Calibrating an analogue pressure sensor
If an analogue pressure sensor is installed on the sprayer, you have to calibrate it before initial use. Calibration determines how high the respective current is when there is no pressure and at maximum pressure.
Procedure
- þ
- You have a reference sensor at hand to measure the pressure.
- ⇨
- The “PRESSURE MEASUREMENT” screen appears.
- ⇨
- The currently measured pressure appears.
- 3.
- Use the reference sensor to verify the pressure of 0 bar.
- 5.
- Switch off the implement to put it in a depressurized state.
- ⇨
- The current is being measured.
- 7.
- Using the pressure regulator, set the maximum system pressure and measure it with an external reference pressure sensor.
- 8.
- Enter the maximum pressure of the flow meter in the “Maximum pressure” parameter.
- ⇨
- The current is being measured.
- 11.
- You have completed the calibration of the analogue pressure sensor.


>
> 
- Open the “CALIBRATION” screen.
- Open the calibration for the zero value.
- Start the calibration for the zero value.
- Open the calibration for the maximum value.