Configuring the fill level sensor
 
If you are working with fill level sensors, they must be configured before using for the first time.
 
 
 
Controls
 
 
 
Use the following function keys to operate the function:
 
 
Function icon
Meaning
Saves the minimum fill level of the tank.
Saves the maximum fill level of the tank.
 
 
 
Procedure
 
 
 
1.
On the work screen, press:
 FS_Maschinendaten > ( FS_weiter_zurück) >  FS_Füllstandssensor_Einstellungen
2.
If you know the minimum and maximum fill levels of the tank, you can optionally enter the “Minimum Volume” and “Maximum Volume” parameters. Otherwise, proceed with the following step:
3.
Empty the tank completely.
4.
 FS_Füllstandssensor_minimum - Save the minimum fill level of the tank.
5.
Fill the tank completely.
6.
 FS_Füllstandssensor_maximum - Save the maximum fill level of the tank.
You have calibrated the fill level sensor.